SEVD-2022-011-03
Vulnerability from csaf_se - Published: 2022-01-11 11:05 - Updated: 2022-03-02 11:05Summary
Easergy P5
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
https://www.se.com/us/en/download/document/7EN52-0390/
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.
We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.
We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.
www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in its Easergy P5 product line.
The Easergy P5 is a medium voltage protection relay.
Failure to apply the mitigations or remediations provided below may risk disclosure of the device
credentials, denial of service, device reboot, or at attacker gaining full control of the relay. This
could result in loss of protection to your electrical network.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of multiple vulnerabilities in its Easergy P5 product line.\r\nThe Easergy P5 is a medium voltage protection relay.\r\nFailure to apply the mitigations or remediations provided below may risk disclosure of the device\r\ncredentials, denial of service, device reboot, or at attacker gaining full control of the relay. This\r\ncould result in loss of protection to your electrical network.",
"title": "Overview"
}
],
"publisher": {
"category": "vendor",
"contact_details": "cybersecurity@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "Easergy P5 - SEVD-2022-011-03 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-011-03\u0026_ga=2.95494236.1781055878.1663751877-1964063624.1663165410"
},
{
"category": "self",
"summary": "Easergy P5 - SEVD-2022-011-03 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-011-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2022-011-03.json"
},
{
"category": "self",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390/"
}
],
"title": "Easergy P5",
"tracking": {
"current_release_date": "2022-03-02T11:05:25.000Z",
"generator": {
"date": "2022-09-21T11:16:51Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.1"
}
},
"id": "SEVD-2022-011-03",
"initial_release_date": "2022-01-11T11:05:25.000Z",
"revision_history": [
{
"date": "2022-01-11T11:05:25.000Z",
"number": "1.0.0",
"summary": "Original Release"
},
{
"date": "2022-03-02T11:05:25.000Z",
"number": "1.1.0",
"summary": "Updated remediation instructions for clarity"
}
],
"status": "final",
"version": "1.1.0"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c 01.401.101",
"product": {
"name": "Schneider Electric Easergy P5 \u003c 01.401.101",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "Easergy P5"
},
{
"branches": [
{
"category": "product_version",
"name": "01.401.101",
"product": {
"name": "Schneider Electric Easergy P5 01.401.101",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "Easergy P5"
},
{
"branches": [
{
"category": "product_version",
"name": "01.303.202",
"product": {
"name": "Schneider Electric Easergy P5 01.303.202",
"product_id": "3"
}
}
],
"category": "product_name",
"name": "Easergy P5"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"acknowledgments": [
{
"names": [
"Timoth\u00e9e Chauvin",
"Paul Noalhyt",
"Yuanshe Wu"
],
"organization": "Red Balloon Security"
}
],
"cve": "CVE-2022-22722",
"cwe": {
"id": "CWE-798",
"name": "Use of Hard-coded Credentials"
},
"notes": [
{
"category": "description",
"text": "A CWE-798: Use of Hard-coded Credentials vulnerability exists that could result in information\r\ndisclosure. If an attacker were to obtain the SSH cryptographic key for the device and take\r\nactive control of the local operational network connected to the product they could potentially\r\nobserve and manipulate traffic associated with product configuration.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2",
"3"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "mitigation",
"details": "For CVE-2022-22723 only, if customers choose not to apply the remediation provided above,\r\nthey should immediately apply the following mitigation to reduce the risk of exploit: \r\nDisable the GOOSE service of the product to reduce the risk of exposure. If GOOSE is needed\r\nfor the application use it only in a secure local area network.\r\nCustomers should use appropriate patching methodologies when applying these patches to\r\ntheir systems. We strongly recommend the use of back-ups and evaluating the impact of these\r\npatches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric\u2019s Customer Care Center if you need assistance removing a patch.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "ADJACENT_NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-22722"
},
{
"acknowledgments": [
{
"names": [
"Timoth\u00e9e Chauvin",
"Paul Noalhyt",
"Yuanshe Wu"
],
"organization": "Red Balloon Security"
}
],
"cve": "CVE-2022-22723",
"cwe": {
"id": "CWE-120",
"name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
},
"notes": [
{
"category": "description",
"text": "A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a\r\nbuffer overflow causing program crashes and arbitrary code execution when specially crafted\r\npackets are sent to the device over the network. Protection functions and tripping function via\r\nGOOSE can be impacted. \r",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2",
"3"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "mitigation",
"details": "For CVE-2022-22723 only, if customers choose not to apply the remediation provided above,\r\nthey should immediately apply the following mitigation to reduce the risk of exploit: \r\nDisable the GOOSE service of the product to reduce the risk of exposure. If GOOSE is needed\r\nfor the application use it only in a secure local area network.\r\nCustomers should use appropriate patching methodologies when applying these patches to\r\ntheir systems. We strongly recommend the use of back-ups and evaluating the impact of these\r\npatches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric\u2019s Customer Care Center if you need assistance removing a patch.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
},
{
"category": "vendor_fix",
"details": "Versions 01.401.101 and 01.303.202 of the Easergy P5 Firmware include a fix for these\r\nvulnerabilities. The version to be used depends on the existing firmware in the Easergy P5. The\r\nfirmware packages are available on request from Schneider Electric\u2019s Customer Care Center\r\nwhich will provide the guidelines on the version to be used. ",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "ADJACENT_NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-22723"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.