SSA-047424

Vulnerability from csaf_siemens - Published: 2025-05-13 00:00 - Updated: 2025-05-13 00:00
Summary
SSA-047424: Code Execution and SQL Injection Vulnerabilities in OZW Web Servers

Notes

Summary
OZW672 and OZW772 Web Server versions contain vulnerabilities that could allow an attacker to execute arbitrary code on the device with root privileges (in versions before V8.0) or to authenticate as Administrator user (in versions before V6.0). Siemens has released new versions for the affected products and recommends to update to the latest versions.
General Recommendations
As a general security measure Siemens strongly recommends to protect network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices in order to run the devices in a protected IT environment.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en",
    "notes": [
      {
        "category": "summary",
        "text": "OZW672 and OZW772 Web Server versions contain vulnerabilities that could allow an attacker to execute arbitrary code on the device with root privileges (in versions before V8.0) or to authenticate as Administrator user (in versions before V6.0).\n\nSiemens has released new versions for the affected products and recommends to update to the latest versions.",
        "title": "Summary"
      },
      {
        "category": "general",
        "text": "As a general security measure Siemens strongly recommends to protect network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices in order to run the devices in a protected IT environment.",
        "title": "General Recommendations"
      },
      {
        "category": "general",
        "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
        "title": "Additional Resources"
      },
      {
        "category": "legal_disclaimer",
        "text": "The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.",
        "title": "Terms of Use"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "productcert@siemens.com",
      "name": "Siemens ProductCERT",
      "namespace": "https://www.siemens.com"
    },
    "references": [
      {
        "category": "self",
        "summary": "SSA-047424: Code Execution and SQL Injection Vulnerabilities in OZW Web Servers - HTML Version",
        "url": "https://cert-portal.siemens.com/productcert/html/ssa-047424.html"
      },
      {
        "category": "self",
        "summary": "SSA-047424: Code Execution and SQL Injection Vulnerabilities in OZW Web Servers - CSAF Version",
        "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-047424.json"
      }
    ],
    "title": "SSA-047424: Code Execution and SQL Injection Vulnerabilities in OZW Web Servers",
    "tracking": {
      "current_release_date": "2025-05-13T00:00:00Z",
      "generator": {
        "engine": {
          "name": "Siemens ProductCERT CSAF Generator",
          "version": "1"
        }
      },
      "id": "SSA-047424",
      "initial_release_date": "2025-05-13T00:00:00Z",
      "revision_history": [
        {
          "date": "2025-05-13T00:00:00Z",
          "legacy_version": "1.0",
          "number": "1",
          "summary": "Publication Date"
        }
      ],
      "status": "interim",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/\u003cV8.0",
                "product": {
                  "name": "OZW672",
                  "product_id": "1"
                }
              },
              {
                "category": "product_version_range",
                "name": "vers:all/\u003cV6.0",
                "product": {
                  "name": "OZW672",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "OZW672"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/\u003cV8.0",
                "product": {
                  "name": "OZW772",
                  "product_id": "3"
                }
              },
              {
                "category": "product_version_range",
                "name": "vers:all/\u003cV6.0",
                "product": {
                  "name": "OZW772",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "OZW772"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2025-26389",
      "cwe": {
        "id": "CWE-78",
        "name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The web service in affected devices does not sanitize the input parameters required for the `exportDiagramPage` endpoint. This could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "1",
          "3"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V8.0 or later version",
          "product_ids": [
            "1",
            "3"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/62567396/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V8.0 or later version",
          "product_ids": [
            "1",
            "3"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/62564534/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 10.0,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1",
            "3"
          ]
        }
      ],
      "title": "CVE-2025-26389"
    },
    {
      "cve": "CVE-2025-26390",
      "cwe": {
        "id": "CWE-89",
        "name": "Improper Neutralization of Special Elements used in an SQL Command (\u0027SQL Injection\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The web service of affected devices is vulnerable to SQL injection when checking authentication data. This could allow an unauthenticated remote attacker to bypass the check and authenticate as\r\nAdministrator user.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "2",
          "4"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V6.0 or later version",
          "product_ids": [
            "2"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/62567396/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V6.0 or later version",
          "product_ids": [
            "4"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/62564534/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "2",
            "4"
          ]
        }
      ],
      "title": "CVE-2025-26390"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…