ssa-953710
Vulnerability from csaf_siemens
Published
2024-05-14 00:00
Modified
2024-05-14 00:00
Summary
SSA-953710: Vulnerabilities in the Network Communication Stack in Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems

Notes

Summary
Several products used in Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems contain buffer overflow vulnerabilities in the network communication stack. Successful exploitation of the vulnerabilities could allow an unauthenticated attacker, who gained access to the fire protection system network, to execute arbitrary code on the affected products (CVE-2024-22039) or create a denial of service condition (CVE-2024-22040, CVE-2024-22041). Product-specific impact of the individual vulnerabilities is documented in the chapter “Vulnerability Description”. Siemens has released new versions for the affected products and recommends to update to the latest versions.
General Recommendations
As a general security measure Siemens strongly recommends to protect network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices in order to run the devices in a protected IT environment.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.



{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en",
    "notes": [
      {
        "category": "summary",
        "text": "Several products used in Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems contain buffer overflow vulnerabilities in the network communication stack. Successful exploitation of the vulnerabilities could allow an unauthenticated attacker, who gained access to the fire protection system network, to execute arbitrary code on the affected products (CVE-2024-22039) or create a denial of service condition (CVE-2024-22040, CVE-2024-22041).\n\nProduct-specific impact of the individual vulnerabilities is documented in the chapter \u201cVulnerability\nDescription\u201d.\n\nSiemens has released new versions for the affected products and recommends to update to the latest versions.",
        "title": "Summary"
      },
      {
        "category": "general",
        "text": "As a general security measure Siemens strongly recommends to protect network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices in order to run the devices in a protected IT environment.",
        "title": "General Recommendations"
      },
      {
        "category": "general",
        "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
        "title": "Additional Resources"
      },
      {
        "category": "legal_disclaimer",
        "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.",
        "title": "Terms of Use"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "productcert@siemens.com",
      "name": "Siemens ProductCERT",
      "namespace": "https://www.siemens.com"
    },
    "references": [
      {
        "category": "self",
        "summary": "SSA-953710: Vulnerabilities in the Network Communication Stack in Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems - HTML Version",
        "url": "https://cert-portal.siemens.com/productcert/html/ssa-953710.html"
      },
      {
        "category": "self",
        "summary": "SSA-953710: Vulnerabilities in the Network Communication Stack in Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems - CSAF Version",
        "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-953710.json"
      },
      {
        "category": "self",
        "summary": "SSA-953710: Vulnerabilities in the Network Communication Stack in Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems - PDF Version",
        "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-953710.pdf"
      },
      {
        "category": "self",
        "summary": "SSA-953710: Vulnerabilities in the Network Communication Stack in Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems - TXT Version",
        "url": "https://cert-portal.siemens.com/productcert/txt/ssa-953710.txt"
      }
    ],
    "title": "SSA-953710: Vulnerabilities in the Network Communication Stack in Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems",
    "tracking": {
      "current_release_date": "2024-05-14T00:00:00Z",
      "generator": {
        "engine": {
          "name": "Siemens ProductCERT CSAF Generator",
          "version": "1"
        }
      },
      "id": "SSA-953710",
      "initial_release_date": "2024-05-14T00:00:00Z",
      "revision_history": [
        {
          "date": "2024-05-14T00:00:00Z",
          "legacy_version": "1.0",
          "number": "1",
          "summary": "Publication Date"
        }
      ],
      "status": "interim",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c MP4",
                "product": {
                  "name": "Cerberus PRO UL Compact Panel FC922/924",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "Cerberus PRO UL Compact Panel FC922/924"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c MP4",
                "product": {
                  "name": "Cerberus PRO UL Engineering Tool",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "Cerberus PRO UL Engineering Tool"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cV4.3.0001",
                "product": {
                  "name": "Cerberus PRO UL X300 Cloud Distribution",
                  "product_id": "3"
                }
              }
            ],
            "category": "product_name",
            "name": "Cerberus PRO UL X300 Cloud Distribution"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c MP4",
                "product": {
                  "name": "Desigo Fire Safety UL Compact Panel FC2025/2050",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "Desigo Fire Safety UL Compact Panel FC2025/2050"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c MP4",
                "product": {
                  "name": "Desigo Fire Safety UL Engineering Tool",
                  "product_id": "5"
                }
              }
            ],
            "category": "product_name",
            "name": "Desigo Fire Safety UL Engineering Tool"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cV4.3.0001",
                "product": {
                  "name": "Desigo Fire Safety UL X300 Cloud Distribution",
                  "product_id": "6"
                }
              }
            ],
            "category": "product_name",
            "name": "Desigo Fire Safety UL X300 Cloud Distribution"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2024-22039",
      "cwe": {
        "id": "CWE-120",
        "name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The network communication library in affected systems does not validate the length of certain X.509 certificate attributes which might result in a stack-based buffer overflow.\r\nThis could allow an unauthenticated remote attacker to execute code on the underlying operating system with root privileges.",
          "title": "Summary"
        },
        {
          "category": "summary",
          "text": "Successful exploitation requires an on-path attacker that intercepts the communication of the engineering tool in the fire system network; code execution might be possible on the underlying operating system with the privileges of the engineering tool user account.",
          "title": "For Cerberus PRO UL Engineering Tool"
        },
        {
          "category": "summary",
          "text": "Successful exploitation requires an on-path attacker that intercepts the communication of the engineering tool in the fire system network; code execution might be possible on the underlying operating system with the privileges of the engineering tool user account.",
          "title": "For Desigo Fire Safety UL Engineering Tool"
        }
      ],
      "product_status": {
        "known_affected": [
          "1",
          "2",
          "3",
          "4",
          "5",
          "6"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to MP4 or later version",
          "product_ids": [
            "1",
            "2",
            "4",
            "5"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V4.3.0001 or later version",
          "product_ids": [
            "3",
            "6"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 10.0,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "1",
            "3",
            "4",
            "6"
          ]
        },
        {
          "cvss_v3": {
            "baseScore": 9.0,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "2"
          ]
        },
        {
          "cvss_v3": {
            "baseScore": 9.0,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "5"
          ]
        }
      ],
      "title": "CVE-2024-22039"
    },
    {
      "cve": "CVE-2024-22040",
      "cwe": {
        "id": "CWE-125",
        "name": "Out-of-bounds Read"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread.\r\nThis could allow an unauthenticated remote attacker to crash the network service.",
          "title": "Summary"
        },
        {
          "category": "summary",
          "text": "Successful exploitation requires an on-path attacker that intercepts the communication of the engineering tool in the fire system network; possible impact is limited to the tool, not the underlying operating system.",
          "title": "For Cerberus PRO UL Engineering Tool"
        },
        {
          "category": "summary",
          "text": "Successful exploitation requires an on-path attacker that intercepts the communication of the engineering tool in the fire system network; possible impact is limited to the tool, not the underlying operating system.",
          "title": "For Desigo Fire Safety UL Engineering Tool"
        }
      ],
      "product_status": {
        "known_affected": [
          "1",
          "2",
          "3",
          "4",
          "5",
          "6"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to MP4 or later version",
          "product_ids": [
            "1",
            "2",
            "4",
            "5"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V4.3.0001 or later version",
          "product_ids": [
            "3",
            "6"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "1",
            "3",
            "4",
            "6"
          ]
        },
        {
          "cvss_v3": {
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "2"
          ]
        },
        {
          "cvss_v3": {
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "5"
          ]
        }
      ],
      "title": "CVE-2024-22040"
    },
    {
      "cve": "CVE-2024-22041",
      "cwe": {
        "id": "CWE-119",
        "name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The network communication library in affected systems improperly handles memory buffers when parsing X.509 certificates.\r\nThis could allow an unauthenticated remote attacker to crash the network service.",
          "title": "Summary"
        },
        {
          "category": "summary",
          "text": "Successful exploitation requires an on-path attacker that intercepts the communication of the engineering tool in the fire system network; possible impact is limited to the tool, not the underlying operating system.",
          "title": "For Cerberus PRO UL Engineering Tool"
        },
        {
          "category": "summary",
          "text": "Successful exploitation requires an on-path attacker that intercepts the communication of the engineering tool in the fire system network; possible impact is limited to the tool, not the underlying operating system.",
          "title": "For Desigo Fire Safety UL Engineering Tool"
        }
      ],
      "product_status": {
        "known_affected": [
          "1",
          "2",
          "3",
          "4",
          "5",
          "6"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to MP4 or later version",
          "product_ids": [
            "1",
            "2",
            "4",
            "5"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V4.3.0001 or later version",
          "product_ids": [
            "3",
            "6"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "1",
            "3",
            "4",
            "6"
          ]
        },
        {
          "cvss_v3": {
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "2"
          ]
        },
        {
          "cvss_v3": {
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "5"
          ]
        }
      ],
      "title": "CVE-2024-22041"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.