icsa-22-298-07
Vulnerability from csaf_cisa
Published
2022-10-25 00:00
Modified
2023-01-18 00:00
Summary
Delta Electronics InfraSuite Device Master
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow an unauthenticated attacker to remotely execute code, cause a denial-of-service condition by remotely deleting files or changing group privileges, or remotely read and write files, all with local administrator privileges.
Critical infrastructure sectors
Energy
Countries/areas deployed
Worldwide
Company headquarters location
Taiwan
Recommended Practices
Delta Electronics also recommends users follow CISA's security recommendations.
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Exploitability
No known public exploits specifically target these vulnerabilities.
{ "document": { "acknowledgments": [ { "names": [ "kimiya" ], "organization": "Trend Micro Zero Day Initiative", "summary": "reporting these vulnerabilities to CISA" }, { "names": [ "Piotr Bazydlo (@chudypb)" ], "organization": "Trend Micro Zero Day Initiative", "summary": "providing updated information for CVE-2022-41657 and CVE-2022-40202" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could allow an unauthenticated attacker to remotely execute code, cause a denial-of-service condition by remotely deleting files or changing group privileges, or remotely read and write files, all with local administrator privileges.", "title": "Risk evaluation" }, { "category": "other", "text": "Energy", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Taiwan", "title": "Company headquarters location" }, { "category": "general", "text": "Delta Electronics also recommends users follow CISA\u0027s security recommendations.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "other", "text": "No known public exploits specifically target these vulnerabilities.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-22-298-07 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-298-07.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-298-07 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-298-07" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-298-07" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" } ], "title": "Delta Electronics InfraSuite Device Master", "tracking": { "current_release_date": "2023-01-18T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-22-298-07", "initial_release_date": "2022-10-25T00:00:00.000000Z", "revision_history": [ { "date": "2022-10-25T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Delta Electronics InfraSuite Device Master (Update A)" }, { "date": "2023-01-18T00:00:00.000000Z", "legacy_version": "A", "number": "2", "summary": "Delta Electronics InfraSuite Device Master (Update A)" } ], "status": "final", "version": "2" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c= 00.00.01a", "product": { "name": "InfraSuite Device Master - Version 00.00.01a and prior", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "InfraSuite Device Master" }, { "branches": [ { "category": "product_version_range", "name": "\u003c 1.0.3", "product": { "name": "InfraSuite Device Master: Version 1.0.3 and prior", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "InfraSuite Device Master" } ], "category": "vendor", "name": "Delta Electronics" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-41778", "cwe": { "id": "CWE-502", "name": "Deserialization of Untrusted Data" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-DataCollect service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization. CVE-2022-41778 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-41778" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-38142", "cwe": { "id": "CWE-502", "name": "Deserialization of Untrusted Data" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-Gateway service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization. CVE-2022-38142 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-38142" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-41779", "cwe": { "id": "CWE-502", "name": "Deserialization of Untrusted Data" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize network packets without proper verification. If the device connects to an attacker-controlled server, the attacker could send maliciously crafted packets that would be deserialized and executed, leading to remote code execution. CVE-2022-41779 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-41779" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-41657", "cwe": { "id": "CWE-22", "name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior allow attacker provided data already serialized into memory to be used in file operation application programmable interfaces (APIs). This could create arbitrary files, which could be used in API operations and could ultimately result in remote code execution. CVE-2022-41657 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-41657" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-41772", "cwe": { "id": "CWE-22", "name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior mishandle .ZIP archives containing characters used in path traversal. This path traversal could result in remote code execution. CVE-2022-41772 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-41772" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-40202", "cwe": { "id": "CWE-306", "name": "Missing Authentication for Critical Function" }, "notes": [ { "category": "summary", "text": "The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution. CVE-2022-40202 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-40202" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-41688", "cwe": { "id": "CWE-306", "name": "Missing Authentication for Critical Function" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lack proper authentication for functions that create and modify user groups. An attacker could provide malicious serialized objects that could run these functions without authentication to create a new user and add them to the administrator group. CVE-2022-41688 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-41688" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-41644", "cwe": { "id": "CWE-306", "name": "Missing Authentication for Critical Function" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lacks authentication for a function that changes group privileges. An attacker could use this to create a denial-of-service state or escalate their own privileges. CVE-2022-41644 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-41644" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-41776", "cwe": { "id": "CWE-306", "name": "Missing Authentication for Critical Function" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to trigger the WriteConfiguration method, which could allow an attacker to provide new values for user configuration files such as UserListInfo.xml. This could lead to the changing of administrative passwords. CVE-2022-41776 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-41776" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-41629", "cwe": { "id": "CWE-306", "name": "Missing Authentication for Critical Function" }, "notes": [ { "category": "summary", "text": "Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to access the aprunning endpoint, which could allow an attacker to retrieve any file from the RunningConfigs directory. The attacker could then view and modify configuration files such as UserListInfo.xml, which would allow them to see existing administrative passwords. CVE-2022-41629 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-41629" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Delta Electronics recommends users uninstall old versions of InfraSuite Device Master and reinstall the updated Version 1.0.3 using the installer.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://datacenter-softwarecenter.deltaww.com/Download/UPS/Software/InfraSuite_Device_Master_1.0.3(x64).exe" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] } ] }
Loading...
Loading...
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.