icsa-23-306-06
Vulnerability from csaf_cisa
Published
2023-11-02 06:00
Modified
2023-11-02 06:00
Summary
Schneider Electric SpaceLogic C-Bus Toolkit

Notes

Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow an attacker to perform remote code execution, which could result in tampering of the SpaceLogic C-Bus home automation system.
Critical infrastructure sectors
Commercial Facilities
Countries/areas deployed
Worldwide
Company headquarters location
France
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Recommended Practices
Do not click web links or open attachments in unsolicited email messages.
Recommended Practices
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Recommended Practices
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "An anonymous researcher"
        ],
        "organization": "Trend Micro\u0027s Zero Day Initiative",
        "summary": "reporting these vulnerabilities to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow an attacker to perform remote code execution, which could result in tampering of the SpaceLogic C-Bus home automation system.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Commercial Facilities",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "France",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Do not click web links or open attachments in unsolicited email messages.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "central@cisa.dhs.gov",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-23-306-06 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2023/icsa-23-306-06.json"
      },
      {
        "category": "self",
        "summary": "ICSA Advisory ICSA-23-306-06 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-306-06"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Schneider Electric SpaceLogic C-Bus Toolkit",
    "tracking": {
      "current_release_date": "2023-11-02T06:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-23-306-06",
      "initial_release_date": "2023-11-02T06:00:00.000000Z",
      "revision_history": [
        {
          "date": "2023-11-02T06:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Initial Publication"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=1.16.3",
                "product": {
                  "name": "SpaceLogic C-Bus Toolkit: \u003c=1.16.3",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "SpaceLogic C-Bus Toolkit"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2023-5402",
      "cwe": {
        "id": "CWE-269",
        "name": "Improper Privilege Management"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Schneider Electric\u0027s SpaceLogic C-Bus Toolkit product is vulnerable due to improper privilege management, which could cause remote code execution when the transfer command is used over the network.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-5402"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Schneider Electric has provided a fix to these vulnerabilities and recommends updating the software to v1.16.4. After installation, it is recommended to reboot the system and verify the version number reflects the new version.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.se.com/au/en/product-range/65976-spacelogic-cbus-lighting-building-automation-system#software-and-firmware"
        },
        {
          "category": "mitigation",
          "details": "If users choose not to apply the remediation provided , they should immediately apply the following mitigation to reduce the risk of exploit: Block TCP Port 20023 to SpaceLogic C-Bus Toolkit by using the rules in the PC firewall.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "By doing this, the vulnerable commands could not then be used to compromise the PC by an external entity as the connection and ultimately the command will not be accepted by SpaceLogic C-Bus Toolkit.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, refer to Schneider Electric\u0027s Security Bulletin SEVD-2023-283-1",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-283-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2023-283-01.pdf"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric strongly recommends the following industry cybersecurity best practices.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Locate control and safety system networks and remote devices behind firewalls andisolate them from the business network.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Place all controllers in locked cabinets and never leave them in the \"Program\" mode.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Never connect programming software to any network other than the network intended for that device.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-5399",
      "cwe": {
        "id": "CWE-22",
        "name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Schneider Electric\u0027s SpaceLogic C-Bus Toolkit product contains a path traversal vulnerability, which could cause tampering of files on the personal computer running C-Bus when using the File Command.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-5399"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Schneider Electric has provided a fix to these vulnerabilities and recommends updating the software to v1.16.4. After installation, it is recommended to reboot the system and verify the version number reflects the new version.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.se.com/au/en/product-range/65976-spacelogic-cbus-lighting-building-automation-system#software-and-firmware"
        },
        {
          "category": "mitigation",
          "details": "If users choose not to apply the remediation provided , they should immediately apply the following mitigation to reduce the risk of exploit: Block TCP Port 20023 to SpaceLogic C-Bus Toolkit by using the rules in the PC firewall.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "By doing this, the vulnerable commands could not then be used to compromise the PC by an external entity as the connection and ultimately the command will not be accepted by SpaceLogic C-Bus Toolkit.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, refer to Schneider Electric\u0027s Security Bulletin SEVD-2023-283-1",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-283-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2023-283-01.pdf"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric strongly recommends the following industry cybersecurity best practices.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Locate control and safety system networks and remote devices behind firewalls andisolate them from the business network.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Place all controllers in locked cabinets and never leave them in the \"Program\" mode.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Never connect programming software to any network other than the network intended for that device.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading...

Loading...

Loading...

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.